Islanding Detection in Microgrids Using Harmonic Signatures
dc.contributor.author | Merino, J. | |
dc.contributor.author | Mendoza-Araya, P. | |
dc.contributor.author | Venkataramanan, G. | |
dc.contributor.author | Baysal, M. | |
dc.contributor.institution | Tecnalia Research & Innovation | |
dc.date.issued | 2015-10-01 | |
dc.description | Publisher Copyright: © 1986-2012 IEEE. | |
dc.description.abstract | In recent years, there has been a growing interest in incorporating microgrids in electrical power networks. This is due to various advantages they present, particularly the possibility of working in either autonomous mode or grid connected, which makes them highly versatile structures for incorporating intermittent generation and energy storage. However, they pose safety issues in being able to support a local island in case of utility disconnection. Thus, in the event of an unintentional island situation, they should be able to detect the loss of mains and disconnect for self-protection and safety reasons. Most of the anti-islanding schemes are implemented within control of single generation devices, such as dc-ac inverters used with solar electric systems being incompatible with the concept of microgrids due to the variety and multiplicity of sources within the microgrid. In this paper, a passive islanding detection method based on the change of the 5th harmonic voltage magnitude at the point of common coupling between grid-connected and islanded modes of operation is presented. Hardware test results from the application of this approach to a laboratory scale microgrid are shown. The experimental results demonstrate the validity of the proposed method, in meeting the requirements of IEEE 1547 standards. | en |
dc.description.status | Peer reviewed | |
dc.format.extent | 8 | |
dc.format.extent | 2056811 | |
dc.identifier.citation | Merino , J , Mendoza-Araya , P , Venkataramanan , G & Baysal , M 2015 , ' Islanding Detection in Microgrids Using Harmonic Signatures ' , unknown , vol. unknown , no. 5 , 6990635 , pp. 2102-2109 . https://doi.org/10.1109/TPWRD.2014.2383412 | |
dc.identifier.doi | 10.1109/TPWRD.2014.2383412 | |
dc.identifier.other | researchoutputwizard: 11556/168 | |
dc.identifier.url | http://www.scopus.com/inward/record.url?scp=84942815365&partnerID=8YFLogxK | |
dc.language.iso | eng | |
dc.relation.ispartof | unknown | |
dc.rights | info:eu-repo/semantics/openAccess | |
dc.subject.keywords | Harmonic signature | |
dc.subject.keywords | Islanding detection method (IDM) | |
dc.subject.keywords | Microgrid | |
dc.subject.keywords | Harmonic signature | |
dc.subject.keywords | Islanding detection method (IDM) | |
dc.subject.keywords | Microgrid | |
dc.subject.keywords | islanding detection method | |
dc.subject.keywords | Energy Engineering and Power Technology | |
dc.subject.keywords | Electrical and Electronic Engineering | |
dc.subject.keywords | Funding Info | |
dc.subject.keywords | This work was supported in part by the Spanish Ministry of Economy and Competitiveness under Grant BES-2010-034386; in part by the United Technologies Research Center through Professional Services Agreements numbered PSA-1159925 under United States Government Contract Number W912HQ-09-C-0055; and PSA-1169296 under United States Government Contract Number DE-EE0003954, TUBITAK-BIDEB 2219 programme; and in part by by CONICYT/FONDAP/15110019. Paper no. TPWRD-00132-2014. | |
dc.subject.keywords | This work was supported in part by the Spanish Ministry of Economy and Competitiveness under Grant BES-2010-034386; in part by the United Technologies Research Center through Professional Services Agreements numbered PSA-1159925 under United States Government Contract Number W912HQ-09-C-0055; and PSA-1169296 under United States Government Contract Number DE-EE0003954, TUBITAK-BIDEB 2219 programme; and in part by by CONICYT/FONDAP/15110019. Paper no. TPWRD-00132-2014. | |
dc.title | Islanding Detection in Microgrids Using Harmonic Signatures | en |
dc.type | journal article |