Show simple item record

dc.contributor.authorHaro-Larrode, Marta
dc.contributor.authorSantos-Mugica, Maider
dc.contributor.authorEguia, Pablo
dc.contributor.authorRodriguez-Sanchez, Raul
dc.contributor.authorGil-de-Muro, Asier
dc.date.accessioned2021-06-18T11:58:49Z
dc.date.available2021-06-18T11:58:49Z
dc.date.issued2020-06
dc.identifier.citationHaro-Larrode, Marta, Maider Santos-Mugica, Pablo Eguia, Raul Rodriguez-Sanchez, and Asier Gil-de-Muro. “Impact of Proportional Resonant Controller Parameters of VSC Connected to AC Grids with Variable X/R Characteristic on the Small Signal Stability.” International Journal of Electrical Power & Energy Systems 118 (June 2020): 105746. doi:10.1016/j.ijepes.2019.105746.en
dc.identifier.issn0142-0615en
dc.identifier.urihttp://hdl.handle.net/11556/1151
dc.description.abstractThe purpose of this paper is to assess the impact of proportional resonant controller (PR) parameters of a Voltage Source Converter (VSC) and AC grid topology on the small signal stability of a VSC-AC system. Based on this, a small signal model is constructed, step by step, and validated against EMT simulations. Following this validation, several scenarios containing different PR controller gains are proposed and compared by means of trajectory of eigenvalues. A discussion of the best adequacy of PR controller parameters and AC grid strength in combination with inductive-resistive characteristic (X/R) is developed to ensure the stability of the system. The previous eigenvalue analysis is verified in time domain by means of EMT simulations. The analysis performed concludes that, while the AC grid strength in combination with PR controller parameters plays an important role in determination of stability, variations in the inductive-resistive AC grid characteristic need to be included in the analysis, since further instabilities can appear even when the PR controller is well designed for a specific AC grid configuration.en
dc.description.sponsorshipThe authors thank the support from the Basque Government (projects: ELKARTEK KK-2017/00083 and Road2DC. KK-2018/00083 and research group GISEL ref. IT1083-16) and from the Ministry of Economy, Industry and Competitiveness (project ENE2016-79145-R AEFI/FEDER, UE).en
dc.language.isoengen
dc.publisherElsevier Ltden
dc.titleImpact of proportional resonant controller parameters of VSC connected to AC grids with variable X/R characteristic on the small signal stabilityen
dc.typearticleen
dc.identifier.doi10.1016/j.ijepes.2019.105746en
dc.rights.accessRightsembargoedAccessen
dc.subject.keywordsVSCen
dc.subject.keywordsSmall signalen
dc.subject.keywordsAC grid strengthen
dc.subject.keywordsProportional-resonant controlleren
dc.subject.keywordsModal analysisen
dc.journal.titleInternational Journal of Electrical Power & Energy Systemsen
dc.page.initial105746en
dc.volume.number118en


Files in this item