    JavaScript is disabled for your browser. Some features of this site may not work without it.

    Fault detection based on ROCOV in a multi-terminal HVDC grid

    View/Open
    260-20-perez.pdf (1.329Mb)
    Identifiers
    URI: http://hdl.handle.net/11556/1004
    DOI: 10.24084/repqj18.260
    Bibliography Export
    RefworksRisMendeleyEndNote
    Statistics
    View Usage Statistics
    Full record
    Show full item record
    Author/s
    Perez-Molina, M.J.; Eguia-Lopez, P.; Larruskain-Eskobal, M.; Etxegarai-Madina, A.; Apiñaniz Apiñaniz, S.
    Date
    2020
    Keywords
    HVDC grid
    ROCOV
    Fault detection
    Protection system
    VSC
    Abstract
    Protection of a meshed VSC-HVDC grid is a challenge due to the behaviour of DC current and voltage signals during fault conditions. Protection systems must operate in a very short time range. Since fault detection should be very fast, local measurement based algorithms are mostly used; communication based algorithms lack the needed speed as a result of the communication time delay. This way, a ROCOV algorithm is proposed in this paper. This algorithm is analysed for different fault conditions.